Listing ID#10041228
ModelKNBL6-63
CategoryCircuit Breakers
Quick answer
RCBO is a Circuit Breakers product. Key specs — Origin: China.
Product Description
Sphere of application:
KNBL6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
KNBL6-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short circuited as well as infre-quent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.
The over-current tripping unit protection feature:
KNBL6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
KNBL6-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short circuited as well as infre-quent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.
Basic specification and main parameters:
| Frame class | 63A |
| Rated working voltage | 240V |
| Rated frequency | 50/60Hz |
| Rated working current | 6,10,16,20,25,32,40,50,63A |
| Rated residual operating current | 0.01,0.03A |
| Rated residual un-operating current | 0.005,0.015 |
| Sensibility | AC Type |
| Maximum operating time | In t≤0.4s , 5In t≤0.01 |
| Instant release type | B,C type |
| Limiting value of un-operating current | 6In |
| Rated limiting short-circuit current | 10000A |
| Pole number | 1P+N |
| Mechanical life | 4000 |
| Electric life | 80000 |
The over-current tripping unit protection feature:
| Sequence NO. | Release | Test current I/In | Start state | Tripping time | Expected restlt |
| 1 | C | 1.13In | Cold state | t≤1h | Not tripping |
| 2 | C | 1.45In | Start right after the serial NO.1 test | t<1h | tripping |
| 3 | C | 2.55In | Cold state | 1s| tripping | |
| 4 | C | 5In | Cold state | t≤0.1s | Not tripping |
| 5 | C | 10In | Cold state | t<0.1s | tripping |