Specifications

Origin
India
Request Quote
Quick answer

India On-Line Pure Sine Wave UPS System is a Power Supplies product. Key specs — Origin: India.

Product Description

Specifications: TECHNICAL SPECIFICATIONS Input Voltage : 230 V AC Single Phase / 415 V AC Three Phase Tolerance : + 15 % Frequency : 50 Hz. Tolerance : + 6% Current Walk In : Ramp Up to Full Load within 30 Sec.

Current Limit : 125% of Full Load I/P Current Power Factor : 0.7 Lag at Nominal I/P Voltage Output Inverter : High Frequency IGBT PWM Capacity : 01 KVA To 100 KVA Voltage : 230 V AC Single Phase / 415 V AC Three Phase Regulation : + 1% Steady state under following conditions. a) I/P Voltage Variation + 15% b) 10% to 100% Load c) DC Voltage Variation From Mini.

To Max. Battery voltage d) Ambient Temperature 0 to 40o C. Frequency : 50 Hz Stability : + 0.1 Hz. Free Running Transient Response : + 8% Max.

Under following Conditions a) Loss or Return of I/P AC Supply b) 100% Step Load Recovery : To Nominal Voltage in Less Than 5 Cycles Harmonic Distortion : THD less than 5% any Single Harmonic less than 2% (With Linear Load from 0 to 100%) Overload Capacity : 125% for 10 Min.

Power Factor : 0.8 Lag to Unity Protections Rectifier : I/P Over voltage, Rectifier soft start, DC Over & Under Voltage, Battery Charging Over Current, I/P MCCB and Fuses at the Bridge I/P Inverter : O/P Over voltage, O/P Over current, short circuit and DC Under Voltage.

Indications : Mains On, Dc On, Inverter On, Inverter Trip, I/P Over voltage, DC Over Voltage, Boost Mode, Float Mode, O/P Over voltage, O/P Over load and Battery Low Alarms : System Trip, O/P Over load, Load On Battery and Battery Low LCD Meter : I/P & O/P AC Voltage, OPTIONAL : DC Voltage & Current, O/P Current and O/P Frequency and Fault Indications Environment Temperature : Operating 0 to 40o C Humidity : 0 to 95% RH Cooling : Forced Air Cooled